Input | |
Voltage | 400 Vac |
Tolerance | 320 – 450V |
Frequency | 50Hz ± 6% |
Output | |
Voltage | 400Vac ± 1% |
Power Factor | 0.8 |
Transfer Time | 0 ms |
Frequency | 50Hz ± 6% (On Mains) |
50Hz ± 0.5% (On Battery) | |
Waveform | Pure Sine Wave |
THDi | Linear Load ≤ 3%; Non-linear Load ≤ 5% |
Crest Factor | 3 : 1 (Max) |
Bypass Facility | Maintenance Bypass and Static Bypass |
DC Bus / DC Functions: | |
DC Bus Voltage | 384V |
Charging Current | 5 – 20A, Adjustable |
Cold-Start Function | Yes |
Battery Charging in OFF Mode | Yes |
Battery Type | Sealed, Maintenance-free VRLA |
LCD User Interface: | |
Metering / Indications for | Voltage |
Load % | |
Frequency | |
General Status | |
Alarm | |
Communication: | |
Interfaces | RS232 |
Overload | |
105~125% | 10 mins (Output swithes to bypass after 60s) |
>130% | 1 min |
Environment: | |
Temperature | 0 ~ 40oC |
Humidity | 20 ~ 90% Non-condensing |
Altitude | < 1000m |
IP Class | 20 |
Physical: | |
Dimensions (mm) | 10-20kVA : 560 x 700 x 1040 (W x D x H) |
30-40kVA : 660 x 800 x 1380 (W x D x H) | |
60-80kVA : 1540 x 880 x 1570 (W x D x H) | |
100-200kVA : 2000 x 980 x 1800 (W x D x H) | |
Weight (Kg) | 10kVA : 260kg |
15kVA : 350kg | |
20kVA : 400kg | |
30kVA : 480kg | |
40kVA : 650kg | |
60kVA : 650kg | |
80kVA : 1200kg | |
100kVA : 1330kg | |
120-200kVA : On Request |
10kVA Vectronic Online UPS FS Series
₦750,000 ₦800,000
Description:
Profie: Tower
Range: 10kVA
Voltage: 400Vac
Frequency: 50Hz
Related products
-
UPS
APC Smart UPS SMC1500I C 1500VA LCD 230V
0 out of 5(0)Output
-
Output power capacity
900Watts / 1.5 kVA
-
Max Configurable Power (Watts)
900Watts / 1.5 kVA
-
Nominal Output Voltage
230V
-
Output Voltage Distortion
Less than 5% at full load
-
Output Frequency (sync to mains)
47 – 53 Hz for 50 Hz nominal, 57 – 63 Hz for 60 Hz nominal
-
Topology
Line Interactive
-
Waveform type
Sine wave
-
Output Connections(8) IEC 320 C13 (Battery Backup)(2) IEC Jumpers (Battery Backup)
Input
-
Nominal Input Voltage
230V
-
Input frequency
50/60 Hz +/- 3 Hz (auto sensing)
-
Input Connections
IEC-320 C14
-
Input voltage range for main operations
180 – 287V
-
Input voltage adjustable range for mains operation
170 – 300V
-
Other Input Voltages
220, 240
Batteries & Runtime
-
Battery type
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
-
Typical recharge time
3hour(s)
-
Replacement Battery
-
Expected Battery Life (years)
3 – 5
-
RBC Quantity
1
-
Runtime
-
Efficiency
Communications & Management
-
Interface Port(s)
USB
-
Control panel
Multi-function LCD status and control console
-
Audible Alarm
Alarm when on battery : distinctive low battery alarm : configurable delays
-
Emergency Power Off (EPO)
—
Surge Protection and Filtering
-
Surge energy rating
459Joules
-
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Physical
-
Maximum Height
219mm , 21.9CM
-
Maximum Width
171mm , 17.1CM
-
Maximum Depth
439mm , 43.9CM
-
Net Weight
24.09KG
-
Shipping weight
27.23KG
-
Shipping Height
376mm , 37.6CM
-
Shipping Width
328mm , 32.8CM
-
Shipping Depth
595mm , 59.5CM
-
Color
Black
-
Master Carton Units
1.0
-
Units per Pallet
18.0
Environmental
-
Operating Temperature
0 – 40 °C
-
Operating Relative Humidity
0 – 95 %
-
Operating Elevation
0-3000meters
-
Storage Temperature
-15 – 45 °C
-
Storage Relative Humidity
0 – 95 %
-
Storage Elevation
0-15000meters
-
Audible noise at 1 meter from surface of unit
45.0dBA
-
Online thermal dissipation
135.0BTU/hr
Conformance
-
Approvals
C-tick, CE, CSA, GOST, UL 1778, VDE
-
Standard warranty
2 years repair or replace
Sustainable Offer Status
-
RoHS
Compliant
-
REACH
REACH: Contains No SVHCs
SKU: n/a -
-
UPS
APC APRBC 140 UPS Replacement Battery Catridge For Select Smart-UPS
0 out of 5(0)Genuine APC replacement battery cartridges (RBC) are tested and certified for compatibility to restore UPS performance to specification
Includes all required connectors, Battery recycling guide, Installation guide, Reusable packagingSKU: n/a