Input | |
Voltage | 400 Vac |
Tolerance | 320 – 450V |
Frequency | 50Hz ± 6% |
Output | |
Voltage | 400Vac ± 1% |
Power Factor | 0.8 |
Transfer Time | 0 ms |
Frequency | 50Hz ± 6% (On Mains) |
50Hz ± 0.5% (On Battery) | |
Waveform | Pure Sine Wave |
THDi | Linear Load ≤ 3%; Non-linear Load ≤ 5% |
Crest Factor | 3 : 1 (Max) |
Bypass Facility | Maintenance Bypass and Static Bypass |
DC Bus / DC Functions: | |
DC Bus Voltage | 384V |
Charging Current | 5 – 20A, Adjustable |
Cold-Start Function | Yes |
Battery Charging in OFF Mode | Yes |
Battery Type | Sealed, Maintenance-free VRLA |
LCD User Interface: | |
Metering / Indications for | Voltage |
Load % | |
Frequency | |
General Status | |
Alarm | |
Communication: | |
Interfaces | RS232 |
Overload | |
105~125% | 10 mins (Output swithes to bypass after 60s) |
>130% | 1 min |
Environment: | |
Temperature | 0 ~ 40oC |
Humidity | 20 ~ 90% Non-condensing |
Altitude | < 1000m |
IP Class | 20 |
Physical: | |
Dimensions (mm) | 10-20kVA : 560 x 700 x 1040 (W x D x H) |
30-40kVA : 660 x 800 x 1380 (W x D x H) | |
60-80kVA : 1540 x 880 x 1570 (W x D x H) | |
100-200kVA : 2000 x 980 x 1800 (W x D x H) | |
Weight (Kg) | 10kVA : 260kg |
15kVA : 350kg | |
20kVA : 400kg | |
30kVA : 480kg | |
40kVA : 650kg | |
60kVA : 650kg | |
80kVA : 1200kg | |
100kVA : 1330kg | |
120-200kVA : On Request |
100kVA Vectronic Online UPS
₦6,900,000 ₦7,200,000
Description:
Profie: Tower
Range: 100kVA
Voltage: 400Vac
Frequency: 50Hz
Related products
-
UPS
Mercury ELITE PRO 1000VA UPS
0 out of 5(0)Mercury ELITE1000 PROELITE1000 PRO
​When it comes to power solutions, you can rest assured when you use Mercury UPS. Mercury offers you a wide range of configurations. No matter you are a home user or you are looking for a corporate solution, you can rely on Mercury UPS.Features:
- Output Short Circuit Protection
- Intelligent Battery Management
- Over Temperature Protection
- Wide Range Of Input Voltage
- Overload Protection
- Auto Restart
- Dataline Protection
- Surge Protection
- DC Start
Specifications:
- Input Voltage 220VAC
- Input Frequency 50Hz
- Input Phase Single Phase
- Input Socket with FUSE
- Cold Start (0~100% load)
- Press the ON / OFF Switch
- Input Range (220V) 140V~285V
- Normal Frequency 50Hz
- Rating Output (VA) 1000VA
- Rating Output (W) 600W
- Waveform Battery Mode (Simulated Sine Wave)AC Mode (Sine Wave)
- Power Factor 0.6
- Rating Voltage 220V
- Output Range 220VAC +17~22%(No Load Connected)
- Rear Output Socket 3x IEC – Battery Backup
- Transfer Time Typical 8ms (max 15ms)
- Short Circuit Protection Line
- Mode FUSE & Software Protection 100%~120% (gives alarm & shut down in 3min)120%~130% (beeps alarm & shut down in 30s)>130% (shut down immediately)
- Battery Mode Software Protection controlled by CPU100%~110% (gives alarm & shut down in 10s)>110% (shut down immediately)
- Battery & Runtime Rating 12V / 9AH x1
- Battery & Runtime Backup Time Typical 8mins~20mins
- Battery & Runtime Change Current 1.5A (max)
- Battery & Runtime Over Charge >14.8V ±0.5 (Stop Charging)
- Battery & Runtime Protection
SKU: n/a
Recently Viewed products
168 Liters Solar Refrigerator
Developed to be energy-efficient and sustainable in most rural places. The dc solar freezer&refrigerator requires very little energy and has a maintenance-free dc compressor.? Equipped with extra-thick insulations, solar freezer&refrigerator can stay cold in? Hot temperatures. Their low frost system reduces the amount of water condensation and ice. An adjustable interior temperature lets you? Keep your fridge/freezer as cold as you like.?
12V 200AH KStar Battery
- 1. ROBUST TUBULAR WITH HIGH PRESSURE DIE CASTED SPINE- RESULTING LOW RATE OF SPINE CORROSION.
- 2. CERAMIC VENT PLUGS- SPECIAL CERAMIC VENT PLUGS FOR CONTROLLED ACID FUMES.
- 3. UNIQUE NEGATIVE PASTE RECIPE FOR HIGH CHARGE ACCEPTANCE
- 4. CONSISTENT BACKUP THROUGHOUT LIFE
- 5. EXCELLENT BEHAVIOR IN PSOC CONDITION
- 6. LOW SELF DISCHARGE
- 7. EXCELLENT PERFORMANCE ON DEEP CYCLIC APPLICATION
- 8. HIGH DESIGN & SERVICE LIFE
- 9. LOW CHANCE OF ACID STRATIFICATION
- 10. AVAILABLE IN FACTORY CHARGED CONDITION FOR READY TO USE