Zektron online UPS TS-11 series adopts online double conversion design and digital control technology and it features high input and output power factor (0.9). With ECO mode for energy-saving, intelligent battery management and excellent network management, it is a cost-effective power solution for your critical devices. When UPS is on battery mode, it can shut down unnecessary load and extend the backup time of the critical load.
80kVA Vectronic Online UPS
₦5,800,000 ₦6,700,000
Description:
Profie: Tower
Range: 80kVA
Voltage: 400Vac
Frequency: 50Hz
Related products
-
UPS
KSTAR Online UPS 10KVA/192V
0 out of 5(0)The Megapower three-phase transformer-less parallel redundancy online UPS series, featured with smallest footprint cabinet, built-in batteries, DSP Control, Common Battery, Programmable battery voltage, intelligent charge mode with powerful battery charger, is an ideal budget-concerned solution to your server, bank, industrial equipment, internet data center, telecom, IT equipment and other mission-critical application.
SKU: n/a -
UPS
Blue Gate 3KVA Online UPS
0 out of 5(0)Blue Gate 3KVA/2100W Online UPS HF Series – BGK 3.0HFi, offers seamless power backup, with zero transfer performance. The Blue Gate Online UPS range has zero switching time, making them ideal for sensitive equipment like servers, networking devices, and similar equipment that will not tolerate any power switchover time. The Blue Gate 3KVA UPS, like others in the series, boasts an advanced UPS design, with a central processing system. It is equipped with advanced voltage compensation technology, advanced frequency technology, and advanced PFC technology. You get undistorted standard sine wave from a wide range of input variables, as a result. Small-Medium network, servers, and other IT equipment Features 1. High frequency and double conversion online technology 2. Fully digitized microprocessor control 3. Wide input voltage range 4. LCD display 5. UPS start-up without battery 6. Cold start 7. Advanced battery management 8. Automatic battery charging in UPS off mode 9. Lightning and surge protection 10. Short circuit and overload protection 11. Fan speed auto control when loads vary 12. Network/fax/modem surge protection 13. An optional extension battery pack 14. Battery voltage display 15. Load capacity display 16. EMI/RFI noise filter 17. Smart RS232 communication with monitoring software 18. Optional SNMP card slot 19. EPO function (optional) 20. Input L and N reversed alarm functionSKU: n/a
Recently Viewed products
20kVA 96V 3 PHASE HDSX SERIES INVERTER
HDSX Inverter
15KVA – 50KVA
The HDSX series Inverter is packed with powerful features such as pure sine wave output, intelligent LCD integration display and an added fault query function, which makes its operation easy to monitor in real time.
The HDSX Series higher KVA solutions offer high quality and reliable power back-up solutions for running such loads, meeting such needs and handling such equipment
HYBRID INVERTER 3KVA/24V/60A
Hybrid Inverter
3KVA
The Hybrid Inverter is packed with powerful features such as pure sine wave output, intelligent LCD integration display and an added fault query function, which makes its operation easy to monitor in real time.
The HDSX Series higher KVA solutions offer high quality and reliable power back-up solutions for running such loads, meeting such needs and handling such equipment
Input | |
Voltage | 400 Vac |
Tolerance | 320 – 450V |
Frequency | 50Hz ± 6% |
Output | |
Voltage | 400Vac ± 1% |
Power Factor | 0.8 |
Transfer Time | 0 ms |
Frequency | 50Hz ± 6% (On Mains) |
50Hz ± 0.5% (On Battery) | |
Waveform | Pure Sine Wave |
THDi | Linear Load ≤ 3%; Non-linear Load ≤ 5% |
Crest Factor | 3 : 1 (Max) |
Bypass Facility | Maintenance Bypass and Static Bypass |
DC Bus / DC Functions: | |
DC Bus Voltage | 384V |
Charging Current | 5 – 20A, Adjustable |
Cold-Start Function | Yes |
Battery Charging in OFF Mode | Yes |
Battery Type | Sealed, Maintenance-free VRLA |
LCD User Interface: | |
Metering / Indications for | Voltage |
Load % | |
Frequency | |
General Status | |
Alarm | |
Communication: | |
Interfaces | RS232 |
Overload | |
105~125% | 10 mins (Output swithes to bypass after 60s) |
>130% | 1 min |
Environment: | |
Temperature | 0 ~ 40oC |
Humidity | 20 ~ 90% Non-condensing |
Altitude | < 1000m |
IP Class | 20 |
Physical: | |
Dimensions (mm) | 10-20kVA : 560 x 700 x 1040 (W x D x H) |
30-40kVA : 660 x 800 x 1380 (W x D x H) | |
60-80kVA : 1540 x 880 x 1570 (W x D x H) | |
100-200kVA : 2000 x 980 x 1800 (W x D x H) | |
Weight (Kg) | 10kVA : 260kg |
15kVA : 350kg | |
20kVA : 400kg | |
30kVA : 480kg | |
40kVA : 650kg | |
60kVA : 650kg | |
80kVA : 1200kg | |
100kVA : 1330kg | |
120-200kVA : On Request |